Isolator Switch (knob/handle)

Load-break isolators that put a visible, lockable break in a circuit so it can be worked on safely.

• 25A to 2000A in 3 pole and 4 pole
• AC-23A to IEC 60947-3 — breaks motor loads, including stalled motor current
• Knob or handle operated with positive ON/OFF indication
• Modular pole construction, all poles including neutral rated at 100%
• Door interlock and padlock facility, telescopic shaft for depth adjustment
• Compact, standard and big-frame variants — use the filters to match panel space

A switch disconnector — isolator, load-break switch, on-load break switch, the names are used interchangeably — does one job well. It breaks a circuit under load and holds it open in a position that is visible, indicated and lockable, so the circuit downstream can be worked on with confidence. It is not a protective device: it has no overload or short-circuit trip and it does not replace an MCCB or a fuse. It is the isolation point.

The distinction that matters when specifying is the utilisation category. These C&S units are AC-23A to IEC 60947-3, which is the category for switching motor loads and means the switch is rated to break a stalled motor current — several times the running current. A device rated AC-21A or AC-22A is only good for resistive or lightly inductive loads. If the feeder runs a pump, a chiller, a lift, an AHU or any other motor, AC-23A is the specification to hold to, and it is also what a consultant’s specification in the UAE will normally call for.

Three pole units switch the phases and leave the neutral solidly linked, which is the normal arrangement for isolating a motor or a sub-distribution feeder on a single supply system. Four pole units switch the neutral as well, and are the right choice where the neutral has to be broken for safety or where the circuit may be fed from a second, separately earthed source.

Frame size is worth filtering on. The same current rating is offered in more than one mechanical frame — the compact series saves depth and width inside a crowded panel, while the standard and big-frame variants give more terminal room and easier cable entry at the same rating. If the panel is already tight, filter to Compact before choosing a rating. Above roughly 630A the frame is set by the current and there is no choice to make.

The construction is modular: single-pole blocks assembled into the pole count you need, which keeps spares simple and lets a damaged pole be replaced instead of the whole switch. Quick make-and-break with self-cleaning contacts keeps the operating speed independent of the operator. A telescopic shaft carries the drive to a door handle at whatever depth the enclosure needs, and the door interlock and padlock facility supports a proper lock-off procedure. Auxiliary contacts (2NO + 2NC) are available where status has to be reported to a BMS or a control scheme.

Use the filters above to narrow by rated current, poles, frame size and build type. All prices are in AED inclusive of 5% VAT, stocked in Dubai for UAE and GCC delivery.