Changeover Switch & Disconnectors

  • Changeover Switch On-Load (Manual)

    13 products
  • DIN Rail / MDB Changeover Switch

    2 products
  • Enclosed Changeover Switch

    2 products
  • Isolator Switch (knob/handle)

    36 products

Manual transfer switches and load-break isolators for distribution boards, generator installations and panel builds.

• Changeover switches 63A–1600A and switch disconnectors 25A–2000A
• 2 pole, 3 pole and 4 pole (with switched neutral)
• Open execution, enclosed and DIN rail / MDB formats
• AC-23A to IEC 60947-3 — rated for motor and inductive loads
• C&S Electric, stocked in Dubai for UAE and GCC delivery

Two different jobs sit in this category and it is worth being clear about which one you are buying. A changeover switch moves a load between two sources of supply — normally the utility incomer and a standby generator — and its defining feature is that it passes through a positive off position so the two sources are never paralleled. A switch disconnector, also called an isolator or a load-break switch, does not choose between sources at all. It puts a visible, lockable break in one circuit so the circuit can be worked on safely, and it is rated to make and break that circuit while it is carrying load.

Both are covered by IEC 60947-3, and the utilisation category on the label is what tells you how hard the device can work. AC-23A, which is what the C&S units here carry, means the switch is rated to break a motor load — including a stalled motor current, which is several times the running current. A device rated only AC-21A or AC-22A is for resistive or mildly inductive loads and should not be used to isolate a pump, chiller, lift or AHU feeder.

Pole count follows the supply. Three pole devices switch the phases and leave the neutral solidly linked. Four pole devices switch the neutral too, which is the requirement on essentially any generator transfer in the UAE, where the utility and the generator have separately earthed neutrals that must be kept apart. Two pole devices handle single-phase supplies, switching line and neutral together.

Format is the other choice. Open execution units are bare mechanisms designed to be mounted on a panel plate by a switchboard builder, and they cover the widest range of ratings. Enclosed units arrive already built into a sheet steel box with a door handle and can go straight on a wall. DIN rail units clip into an existing MDB alongside the MCBs and are the neat answer below 63A.

Use the filters above to narrow by rated current, poles, build type and frame size. Everything listed is held in Dubai stock with AED pricing inclusive of 5% VAT. If you have a single line diagram or a board schedule, send it over — we will confirm ratings, pole configuration and accessories and quote the complete list.